Page 53
Link Assignment
A Link Assignment is used when two Access Control Readers are used to control access to the same door (i.e. one
reader on the inside and the other on the outside of the restricted door). This is useful when an Access Control Card
or Key Tag is required to enter or exit through a restricted door.
Since the door lock is physically connected to a single Access Control Reader, the Link Assignment links the selected
Access Control Reader with a second Access Control Reader so that when a valid Access Control Card or Key Tag is
presented at either Access Control Reader, the door is unlocked. Furthermore, the controller will log which Access
Control Reader was used to access the door (i.e. whether the user was entering or exiting the door).
READER 1 LINKED TO: 0
0-4
Enter the number of the Access Control Reader that will be linked to the selected reader, followed by the ' # ' key.
Notes:
Only two Access Control Readers can be linked together.
When a valid Access Control Card of Key Tag is presented at either linked Access Control Reader, all LED
indicators on both of the linked Access Control Readers will illuminate the color of the current security arming state
and will remain illuminated while the door is unlocked.
Unlock Time
The Unlock Time is the amount of time that the door remains unlocked when a valid Access Control Card or Key Tag
is presented at the Access Control Reader. The Unlock Time can be between 1-60 seconds and is individually
configured for each reader.
Note: When the door is unlocked due to a valid Access Control Card or Key Tag is presented, all LED indicators will
illuminate the color of the current security arming state and will remain illuminated while the door is unlocked.
READER 1 UNLK TIME: 5
1-60 SECONDS
Enter the Unlock Time (1-60 seconds) for the selected Access Control Reader, followed by the ' # ' key. The default
time is 5 seconds.
Exit Time
The Exit Time is the amount of time that the door remains unlocked when the “Request to Exit” input is tripped. An
optional device, such as a Request to Exit” button which is mounted on the inside of the restricted door, is used to
unlock the door without requiring a second Access Control Reader. The Exit Time can be between 1-60 seconds and
is individually configured for each reader.
Note: When the door is unlocked due to pressing a “Request to Exit” button, none of the LED indicators will illuminate.
READER 1 EXIT TIME: 5
1-60 SECONDS
Enter the Exit Time (1-60 seconds) for the selected Access Control Reader, followed by the ' # ' key. The default time
is 5 seconds.