ARMING CONFIRMATION
The Arming Confirmation is a quick pulse (squawk) given by the outside siren when the alarm system is armed into a
security mode and the EXIT DELAY is expired.
ARMING CONFIRMATION: 0
0=NO 1=YES
To enable the arming confirmation feature, press the 1 (YES) key, then press the ' # ' key.
The default setting is 0 (NO) disabled.
FIRE ALARM VERIFICATION
This unit is equipped with a FIRE ALARM VERIFICATION feature. When enabled, if a zone configured as a FIRE
(Type 32) or a GAS (Type 34) is activated, the system will cycle SWITCH 12V and Switched Power Outputs off for 10
seconds. The SWITCH 12V power output will then be restored, and 5 seconds later, the zones will be monitored
again. If the zone is activated again within a 2-minute window, the fire alarm will be activated. If not, no fire alarm will
be indicated.
VERIFY FIRE ALARMS: 0
0=NO 1=YES
This feature is turned OFF by factory default.
If VERIFY FIRE ALARMS is turned ON:
1) Any device (other than FIRE or GAS) connected to a SWITCH 12V Output (i.e. Glassbreak Detectors), must
be connected to a zone configured as a LATCHING ZONE TYPE.
2) The following notice is required by UL:
WARNING
This unit includes an alarm verification feature that will result in a delay of the system fire alarm signal from the
initiating circuit. The total delay (Omni LTe controller plus detector delay) shall not exceed 60 seconds. No other
initiating devices shall be connected to these circuits unless approved by the local authority having jurisdiction.
Zone Control Detector Total Delay
Circuit Unit Delay Model/Delay
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
________ : 10 seconds + ______________ = __________________
SUPERVISE INT SNDR
This enables or disables supervision of the Interior Horn Output, which monitors the wiring to the connected sirens.
Factory default is disabled.