EasyManuals Logo

LG multi V PLUS Service Manual

LG multi V PLUS
373 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
Service Manual 37
Specifications
2.1.2 Heat Pump
Heat Pump (50Hz)
Notes:-
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. L.E.V.:Linear Expansion Valve
Conversion Formula
Kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
3
/min x 35.3
Model Unit
W
Cooling Capacity kcal/h
Btu/h
W
Heating Capacity kcal/h
Btu/h
Casing
Body
mm
Dimensions (W*H*D)
inch
Front Panel
mm
inch
Coil
Rows x Columns x FPI
Face Area m
2
Type
Motor Output W
Running Current A
Fan Air Flow Rate(H/M/L) cmm
cfm
Drive
Speed control
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Liquid Side mm(inch)
Pipe Connections
Gas Side mm(inch)
Drain Pipe(OD)
mm
Net Weight kg(lbs)
Noise Level
(Sound Press, 1.5m, H/M/L)
dBA±3
Power Supply Ø / V / Hz
Refrigerant Control
Power cable mm
2
Transmission cable mm
2
Panel Color
Stuffing Quantity Without S/parts
20/40ft
LRNN126TEA(C)0 LRNN186TEA(C)0 LRNN216TDA(C)0
3,500 5,300 6,200
3,009 4,557 5,331
11,942 18,084 21,155
3,938 5,963 6,975
3,385 5,127 5,997
13,435 20,345 23,800
Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
570*570*269 570*570*269 840*840*290
22.4*22.4*10.5 22.4*22.4*10.5 33.0*33.0*11.4
670*670*30 670*670*30 950*950*30
26.4*26.4*1.2 26.4*26.4*1.2 37.4*37.4*1.2
2*11*19 2*11*19 2*12*21
0.27 0.27 2*0.26
Turbo Fan Turbo Fan Turbo Fan
20 25 60
0.69 0.69 0.80
11/10/9 13/12/10 18/15.9/13.9
389/353/318 459/424/353 636/562/491
Direct Direct Direct
Phase Control Phase Control Phase Control
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene Foamed polystrene Foamed polystrene
F
use, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor
Ø6.35(1/4) Ø9.52(3/8) Ø9.52(3/8)
Ø12.7(1/2) Ø15.88(5/8) Ø15.88(5/8)
32.0 32.0 32.0
19(41.9) 19(41.9) 32(70.5)
38/35/32 41/39/37 40/37/35
1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50 1 / 220 ~ 240 / 50
LEV LEV LEV
CV2.0 X 3C CV2.0 X 3C CV2.0 X 3C
CVV-SB 1.25 X 2C CVV-SB 1.25 X 2C CVV-SB 1.25 X 2C
White White White
189/378 189/378 72/144