EasyManua.ls Logo

LG SV-iS5 - Page 133

LG SV-iS5
205 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 6 - Parameter Description [I/O]
127
frequencies are applied when the multi-function input
terminals (P1, P2, P3, RST, BX, JOG, FX and RX) select
the step. See [Speed-L, Speed-M, Speed-H, Speed-X] in
I/O-12 ~14, I/O-33.
Step
Freq.
Code
Spd-X
Spd-H
(P3)
Spd-
M(P2)
Spd-L
(P1)
Jog
Ter.
Step
Freq-0
DRV-00
0 0 0 0 0
Jog I/O-20
X X X X 1
Step
Freq-1
DRV-05
0 0 0 1 0
Step
Freq-2
DRV-06
0 0 1 0 0
Step
Freq-3
DRV-07
0 0 1 1 0
Step
Freq-4
I/O-21
0 1 0 0 0
Step
Freq-5
I/O-22
0 1 0 1 0
Step
Freq-6
I/O-23
0 1 1 0 0
Step
Freq-7
I/O-24
0 1 1 1 0
Step
Freq-8
I/O-85
1 0 0 0 0
Step
Freq-9
I/O-86
1 0 0 1 0
Step
Freq-10
I/O-87
1 0 1 0 0
Step
Freq-11
I/O-88
1 0 1 1 0
Step
Freq-12
I/O-89
1 1 0 0 0
Step
Freq-13
I/O-90
1 1 0 1 0
Step
Freq-14
I/O-91
1 1 1 0 0
Step
Freq-15
I/O-92
1 1 1 1 0
7- 0: OFF, 1: ON, X: Jog
** Speed-X: The highest speed input bit (used when one of
RST, BX, JOG, FX, RX set to Speed-X)
I/O-20 [Jog Frequency] can be used as one of the step
frequencies.
If the Jog terminal is ON, inverter operates to Jog
frequency regardless of other terminal inputs.
[JOG and Multi-Step Operation]
I/O-25 ~ I/O-38: 1
st
~ 7
th
Accel/Decel Time
These codes are applied when the multi-function input
terminals (P1, P2, P3) select the Accel/Decel time. See
[XCEL-L, XCEL-M, XCEL-H] in I/O-12 ~ I/O-14.
Related Functions:
DRV
-
04 [Frequency mode]
DRV-05 ~ DRV-07 [Step Frequency 1 ~ 3]
I/O-12 ~ 14, 93~97 [Multi-function inputs]
I/O-17 [Filtering Time Constant]
I/O?
Acc time-1
25 20.0 sec
20.00
25
Factory Default: 20.0 sec 20.0
I/O?
Dec time-7
38 20.0 sec
20
38
Factory Default: 20.0 sec 20.0
Related Functions:
DRV
-
01 ~ DRV
-
02 [Accel/Decel Time]
FU2-70 [Reference Freq. for Accel/Decel]
FU2-71 [Accel/Decel Time Scale]
I/O-12 ~ I/O-14 [Multi-function inputs]
P1-CM
ON
ON
Output Frequency
Time
Time
P2-CM
ON
ON
Time
P3-CM
ON
Time
JOG-CM
ON
Time
FX-CM
ON
Time
RX-CM
ON
Time
O
N
ON
Step
0
Step
1
Step
2
Step
3
Step
4
Step
5
Step
6
Step
7
Jog
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu

Table of Contents

Other manuals for LG SV-iS5

Related product manuals