EasyManuals Logo

LG SV-iS5 User Manual

LG SV-iS5
205 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
VI
(9) UL Marking
1. Short Circuit Rating
Suitable For Use On A Circuit Capable Of Delivering Not More Than Table1 RMS Symmetrical
Amperes, 240V for 240V rated inverters, 480V for 480V rated inverters Volts Maximum,
Table 1. RMS Symmetrical Amperes for iS5 series.
Model Rating
SV008iS5-2, SV008iS5-4, SV015iS5-2, SV015iS5-4, SV022iS5-2, SV022iS5-4,
SV037iS5-2, SV037iS5-4,SV055iS5-2, SV055iS5-4, SV075iS5-2, SV075iS5-4,
SV110iS5-2, SV110iS5-4, SV150iS5-2, SV150iS5-4,SV185iS5-2, SV185iS5-4,
SV220iS5-2, SV220iS5-4, SV3005iS5-2, SV300iS5-4, SV370iS5-2, SV370iS5-4
5,000A
SV450iS5-2, SV450iS5-4, SV550iS5-2, SV550iS5-4, SV750iS5-4, 10,000A
2. OVERLOAD PROTECTION
IOLT: IOLT(inverter Overload Trip) protection is activated at 150% of the inverter rated current for
1 minute and greater.
OLT : Inverter shuts off its output when inverter output current exceeds its overload trip level for
overload trip time. OLT is selected when FU1-56 is set to Yes and activated at 120% of FU1-57
[Motor rated current] for 60 sec set in FU1-58.
3. OVER SPEED PROTECTION
Not Provided With Overspeed Protection.
4.Risk of Electric Shock
More than one disconnect switch may be required to de-energize the equipment before servicing.
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu

Table of Contents

Other manuals for LG SV-iS5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG SV-iS5 and is the answer not in the manual?

LG SV-iS5 Specifications

General IconGeneral
BrandLG
ModelSV-iS5
CategoryController
LanguageEnglish

Related product manuals