Chapter 5 - Parameter List
64
5.4 Input/Output Group [I/O]
Keypad Display Setting Range
Code
Description
LCD 7-Segment
Filtering Time Constant
for V1 Signal Input
V1 filter 01 0 to 9999 [ms] 1 10 [ms]
V1 Input Minimum
Voltage
V1 volt x1 02 0 to 10 [V] 0.01
Frequency
Corresponding to V1
Input Minimum Voltage
V1 freq y1/
V1 [%] y1
03
0 to FU1-20 [Hz]/
0-150 [%]
0.01
V1 Input Maximum
Voltage
V1 volt x2 04 0 to 10 [V] 0.01
Frequency
Corresponding to V1
Input Maximum Voltage
V1 freq y2/
V1 [%] y2
05
0 to FU1-20/
0-150 [%]
0.01
Filtering Time Constant
for I Signal Input
I filter 06 0 to 9999 [ms] 1 10 [ms]
I curr x1 07 0 to 20 [mA] 0.01
Frequency
Corresponding to I Input
Minimum Current
I freq y1/
I [%] y1
08
0 to FU1-20
0-150 [%]
0.01
I curr x2 09 0 to 20 [mA] 0.01
Frequency
Corresponding to I Input
Maximum Current
I freq y2/
I [%] y2
10
0 to FU1-20/
0-150 [%]
0.01
None 0
half of x1 1
I/O-11
Criteria for Analog Input
Signal Loss
Wire broken 11
below x1 2
- None Yes
Speed-L 0
Speed-M 1
Speed-H 2
XCEL-L 3
XCEL-M 4
XCEL-H 5
Dc-brake 6
2nd Func 7
Exchange 8
- Reserved - 9
Up 10
Down 11
3-Wire 12
Ext Trip-A 13
Ext Trip-B 14
iTerm Clear 15
Open-loop 16
I/O-12
Multi-Function Input
Terminal ‘P1’ Define
P1 define 12
Main-drive 17
- Speed-L
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu