Chapter 5 - Parameter List
67
Keypad Display Setting Range
Code
Description
LCD 7-Segment
LCD 7-Segment
Units
Factory
Default
Adj.
During
Run
Page
I/O-45
Fault Output Relay
Setting (30A, 30B, 30C)
Relay mode 45
000 to 111
(Bit Set)
- 010 Yes
133
I/O-46
26
Inverter Number Inv No. 46 1 to 31 1 1 Yes
133
1200 bps 0
2400 bps 1
4800 bps 2
9600 bps 3
I/O-47
Baud Rate Baud rate 47
19200 bps 4
- 9600 bps
Yes
133
None 0
FreeRun 1
I/O-48
Operating selection at
Loss of Freq. Reference
Lost command
48
Stop 2
- None Yes
I/O-49
Waiting Time after Loss
of Freq. Reference
Time out 49 0.1 to 120 [sec] 0.1
1.0 [sec]
Yes
133
None 0
Auto-A 1
I/O-50
Auto (Sequence)
Operation selection
Auto mode 50
Auto-B 2
- None No
I/O-51
Sequence Number
Selection
Seq select 51 1 to 5 1 1 Yes
I/O-52
The Number of Steps of
Sequence Number #
Step number 52 1 to 8 1 2 Yes
134
I/O-53
27
1
st
Step Frequency of
Sequence 1
Seq1 / 1F 53 0.01 to FU1-20 0.01
11.00 [Hz]
Yes
I/O-54
Transient Time to 1
st
Step
of Sequence 1
Seq1 / 1T 54 0.1 to 6000 [sec] 0.1
1.1 [sec]
Yes
I/O-55
Steady Speed Time at 1
st
Step of Sequence 1
Seq1 / 1S 55 0.1 to 6000 [sec] 0.1
1.1 [sec]
Yes
Reverse 0
I/O-56
Motor Direction of 1
st
Step of Sequence 1
Seq1 / 1D 56
Forward 1
- Forward
Yes
I/O-57
1
st
Step Frequency of
Sequence 2
Seq1 / 2F 57 0.01 to FU1-20 0.01
21.00 [Hz]
Yes
135
I/O-58
Transient Time to 1
st
Step
of Sequence 2
Seq1 / 2T 58 0.1 to 6000 [sec] 0.1
1.1 [sec]
Yes
I/O-59
Steady Speed Time at 1
st
Step of Sequence 2
Seq1 / 2S 59 0.1 to 6000 [sec] 0.1
1.1 [sec]
Yes
Reverse 0
I/O-60
Motor Direction of 1
st
Step of Sequence 2
Seq1 / 2D 60
Forward 1
- Forward
Yes
135
I/O-85
Step Frequency 8 Step freq-8 85 20.00 [Hz]
Yes
I/O-86
Step Frequency 9 Step freq-9 86 10.00 [Hz]
Yes
I/O-87
Step Frequency 10 Step freq-10 87 20.00 [Hz]
Yes
I/O-88
Step Frequency 11 Step freq-11 88 30.00 [Hz]
Yes
I/O-89
Step Frequency 12 Step freq-12 89
0 to FU1-20 0.01
40.00 [Hz]
Yes
126
26
Code I/O-46 through I/O-49 are used in Option Board like RS485, Device, Net and F-net etc.
27
The Seq# of code I/O-53 through I/O-60 varies according to the sequence number selected in I/O-51.
The parameter code may be extended to I/O-84 depending the number of steps set in I/O-52 because the steps can be set up to 8.