EasyManua.ls Logo

Littelfuse MPS - Earth-Fault-CT Input; Voltage Inputs; Motor Data; Output Relay Assignment

Littelfuse MPS
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 4-2
MPS Motor Protection System Rev. 6-F-022117
Operation and Setup
4.2.4 EARTH-FAULT-CT INPUT
OPI Menu: Setup | System Ratings | EF-CT Primary
The setting range for the earth-fault-CT-primary rating
is 1 to 5,000 A. The CT-primary rating is 5 A for
sensitive CT’sEFCT-1 and EFCT-2.
4.2.5 VOLTAGE INPUTS
OPI Menu: Setup | System Ratings
Select the voltage-connection type (1 PT line-line, 2 PT
line-line, 3 PT line-neutral/direct) to enable voltage-
measuring functions. System Voltage is the system line-
to-line voltage. The system voltage range is 120 V to
25 kV. For the 1-PT and 2-PT connections, Input Voltage
is the PT-secondary voltage when system voltage is
applied. For the 3-PT connection, the Input Voltage is the
PT-secondary line-to-line voltage. For the direct
connection, set Input Voltage the same as the System
Voltage setting. In all cases, line-to-line voltages are
displayed.
Voltage unbalance will indicate if the voltage
sequence is B-A-C. If B-A-C sequence is indicated,
correct the PT connections so that power measurements
will be valid.
NOTE: The 1-PT connection does not allow detection of
voltage unbalance.
NOTE: B-A-C sequence will cause a trip if voltage
phase-reverse protection is enabled.
4.2.6 MOTOR DATA
OPI Menu: Setup | System Ratings
OPI Menu: Setup | Protection Overload
Motor data must be entered for the FLA Rating,
Frequency, and Service Factor. If a tachometer is used,
the Sync Speed is required. If the starter selected requires
two FLA ratings, FLA Rating 2 must be entered.
The Frequency setting determines the sampling rate
used by the MPS for current and voltage measurements.
If Sync to ASD is selected as the analog-input type, the
Frequency setting is not used and the analog output from
an adjustable-speed drive determines the sampling rate
used by current- and voltage-measuring algorithms. See
Section 5.29.2.
Locked-rotor current, cold locked-rotor time, and hot
locked-rotor time must be entered in the Protection |
Overload menu to provide customized overload
protection. See Section 5.2.
4.2.7 OUTPUT RELAY ASSIGNMENT
OPI Menu: Setup | Relay Outputs | Relay x
Each of the five output relays can be assigned to one of
the functions listed in Table 4.1. More than one relay can
be assigned the same function. Note that Relay 5 is a
solid-state relay with a low current rating and should only
be used for interlocks or annunciation.
Relay assignments Starter RLYA, Starter RLYB, Starter
RLYC, and Starter RLYD operate in conjunction with
MPS starting functions to control the motor-starter
contactor(s). See Section 6. Contactor status can be
monitored using auxiliary contacts and the digital inputs.
See Section 4.2.8 and Figs. 6.9 to 6.23.
TABLE 4.1 OUTPUT-RELAY FUNCTIONS
FUNCTION
ASSIGNMENT OR ACTION
Starter RLYA
Relay is assigned to the Starter Relay A
function.
Starter RLYB
Relay is assigned to the Starter Relay B
function.
Starter RLYC
Relay is assigned to the Starter Relay C
function.
Starter RLYD
Relay is assigned to the Starter Relay D
function.
Trip1
Relay operates when a trip occurs in a
protective function assigned Trip1, Trip1&2,
Trip1&3, or Trip1,2,&3. Fail-safe or non-fail-
safe mode selection is active.
Trip1 Pulse
(1)
Trip1 energizes the relay for the time duration
specified by the RY Pulse Time set point.
Trip2
Relay operates when a trip occurs in a
protective function assigned Trip2, Trip1&2,
Trip2&3, or Trip1,2,&3. Fail-safe or non-fail-
safe mode selection is active.
Trip3
Relay operates when a trip occurs in a
protective function assigned Trip3, Trip1&3,
Trip2&3, or Trip1,2,&3. Fail-safe or non-fail-
safe mode selection is active.
Alarm1
Relay operates when an alarm occurs in a
protective function assigned Alarm1,
Alarm1&2, Alarm1&3, or Alarm1,2,&3. Fail-
safe or non-fail-safe mode selection is active.
Alarm2
Relay operates when an alarm occurs in a
protective function assigned Alarm2,
Alarm1&2, Alarm2&3, or Alarm1,2,&3. Fail-
safe or non-fail-safe mode selection is active.
Alarm3
Relay operates when an alarm occurs in a
protective function assigned Alarm3,
Alarm1&3, Alarm2&3, or Alarm1,2,&3. Fail-
safe or non-fail-safe mode selection is active.
Local
Relay energized when Local starter control is
selected.
Interlock
Relay is energized when all digital-input
interlocks are completed.
Current
Relay is energized when current is detected.
Run Mode
Relay is energized when motor is running.
(Current <125% for Run-Mode Delay)
Sequence
Complete
Relay is energized when the starter
Start Time has elapsed.
Start Inhibit
Relay is energized when in an I
2
t or
starts-per-hour inhibit condition.
Watchdog
Relay is energized when the supply voltage is
applied and the MPS is operating properly.
Reduced OC
Relay is energized when in maintenance mode
(ROC = On).
None
(2)
No Assignment (Default).
(1)
Assign this function to only one relay. Non-fail-
safe operation only.
(2)
Relay outputs must be assigned. Default is None.

Table of Contents