EasyManua.ls Logo

Littelfuse MPS - Locked-Rotor Times; Emergency Thermal Reset; Trip Time; Status Messages

Littelfuse MPS
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 5-4
MPS Motor Protection System Rev. 6-F-022117
Protective Functions
5.2.2 LOCKED-ROTOR TIMES
In all cases, values for T
H
and T
C
should be obtained
from the motor manufacturer. The following information
is provided to assist in selecting values for T
H
and T
C
only
if manufacturer data is not available.
Heater-style overload elements are available as
Class 10, Class 20, or Class 30. Class 20 is recommended
for general applications, Class 10 is used for motors with
short locked-rotor time capability, and Class 30 is used in
high-inertia applications to allow additional accelerating
time where motors are within Class-30 performance
requirements. These overloads can be replicated by
setting T
C
= 10, 20, or 30 s; T
H
= 0.1 s; and Locked-Rotor
Current = 6.00 x FLA.
An induction motor built to the NEMA MG 1 standard
is capable of:
two starts in succession (coasting to rest between
starts) with the motor initially at ambient temperature
(cold start)
one start with the motor initially at a temperature not
exceeding its rated-load operating temperature (hot
start).
Since the connected load has a direct influence on
motor heating during a start, NEMA MG 1 defines the
load torque and the load inertia (Wk
2
) for these starts as a
function of the motor’s rated power and synchronous
speed. To satisfy the cold-start requirement, a start must
not use more than 50% thermal capacity. To satisfy the
hot-start requirement, used thermal capacity at steady
state must be less than 50%.
If the thermal model in the MPS has the correct value
of T
C
and if Used I
2
t increases by 50% during a start, the
load is equal to the NEMA-defined load and two starts
from cold will be permitted. If Used I
2
t increases by more
than 50% during a start, the load is greater than the
NEMA-defined load and two starts from cold should not
be permitted a delay is required between starts. The
appropriate delay can be obtained by enabling I
2
t Start
Inhibit and setting the I
2
t Inhibit Level equal to 100%
minus the I
2
t used during a start (a slightly lower level is
recommended to allow for supply and load variations). If
Used I
2
t increases by less than 50% during a start, the
load is less than the NEMA-defined load and two starts
from cold will be permitted.
The magnitude of T
H
relative to T
C
determines if a hot
start will be permitted if I
2
t Start Inhibit is enabled and the
I
2
t Inhibit Level is set as described above. If Used I
2
t
increases by 50% or less during a start, a hot start will be
permitted if T
H
is equal to or greater than 50% of T
C
.
Increasing T
H
above 50% of T
C
is not recommended
unless specific information is available with respect to T
H
.
5.2.3 EMERGENCY THERMAL RESET
OPI Menu: Messages | Emerg I2t Reset | Reset I2t Memory
Emergency Thermal Reset (ETR) sets Used I
2
t to 0%,
resets starts-per-hour variables, and disables PTC and
RTD temperature trips. Program access (password) is
required. Disabled-temperature protection is indicated by
t
°
Disabled by ETR in the Status Messages display. If
PTC or RTD temperature protection is not enabled, t
°
Disabled by ETR will not be displayed. Stator RTD or
PTC trips are reset when ETR is performed regardless of
measured temperatures. Temperature protection must be
re-enabled in the Messages | Emerg I
2
t Reset | Reenable
Temp menu, or by cycling supply voltage.
Temperature alarms and sensor verification remain
enabled during ETR.
NOTE: Temperature protection is not automatically re-
enabled after an Emergency Thermal Reset.
5.3 OVERCURRENT
OPI Menu: Setup | Protection | Overcurrent
Overcurrent protection is based on the largest
fundamental-frequency component (DFT) of the three
phase currents. An alarm-level setting is not provided.
When enabled, overcurrent protection is active at all
times. It is not bypassed during a start.
Trip Level ............................. 1.00 to 15.00 x CT-Primary
Rating (I
p
)
Trip Delay (TD) .................... 0.00 to 10.00 s
(See Tables 5.1 and 5.2)
Protection .............................. Enable/Disable Trip1, 2, 3
Measurement Method ........... DFT
TABLE 5.1 TRIP TIME
FAULT LEVEL
(multiples of trip-
level setting)
(1)
TRIP RELAYS
(ms)
(± 10 ms)
STARTER
RELAYS (ms)
(± 15 ms)
2
5
10
18
TD + 35
TD + 30
TD + 27
TD + 26
TD + 45
TD + 40
TD + 37
TD + 36
(1)
For overcurrent faults less than 18 x I
p
.
For earth faults less than 1 x I
e
.
TABLE 5.2 FAULT DURATION REQUIRED FOR TRIP
FAULT LEVEL
(multiples of trip-
FAULT DURATION
(ms)
level setting)
(1)
TD 20 ms
TD > 20 ms
2
5
10
18
10
5
2
1
TD 10
TD 15
TD 18
TD 19
(1)
For overcurrent faults less than 18 x I
p
.
For earth faults less than 1 x I
e
.

Table of Contents