Chapter 7 Input/Output Specifications
7-28
7.7 Combined Module Digital Output Specification
7.7.1 8 point relay output part
Model
Specification
Relay output module
XBE-DR16A
Output point 8 point
Insulation method Relay insulation
Rated load voltage/current
DC24V 2A(resistive load ) / AC220V 2A(COSΨ = 1), 5A/COM
Min. load voltage/current
DC5V / 1
Max. load voltage AC250V, DC125V
Off leakage current 0.1 (AC220V, 60 )
Max. On off frequency 3,600 times / hour
Surge absorber None
Life time
Mechanical 200 million or above
Electrical
Rated load voltage / current 1 million or above
AC200V / 1.5A, AC240V / 1A (COSΨ = 0.7) 1 million or above
AC200V / 1A, AC240V / 0.5A (COSΨ = 0.35) 1 million or above
DC24V / 1A, DC100V / 0.1A (L / R = 7 ) 1 million or above
Response
time
Off On
10 or less
On Off
12 or less
Common method
8 / COM
Proper cable Size
Stranded wire 0.3~0.75 (External diameter 2.8 or less)
Consumption current
280 (when all point On)
Operation indication Output On, LED On
External connection
method
9 pin connector
Weight 81g
Circuit configuration No.
Contact
Type
TB1 0
TB2 1
TB3 2
TB4 3
TB5 4
TB6 5
TB7 6
TB8 7
TB9 COM
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
DC5V
RY
Internal
circuit
Terminal
block no.
TB1
TB9
TB8

Table of Contents