EasyManuals Logo

LSIS XEC-DR64H User Manual

LSIS XEC-DR64H
236 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #183 background imageLoading...
Page #183 background image
Chapter 9. Installation and Wiring
9-18
9.3.4
Specifications of wiring cable
The specifications of cable used for wiring are as follows.
Types of external
connection
Cable specification (mm
2
)
Lower limit Upper limit
Digital input 0.18 (AWG24) 1.5 (AWG16)
Digital output 0.18 (AWG24) 2.0 (AWG14)
Analogue I/O 0.18 (AWG24) 1.5 (AWG16)
Communication 0.18 (AWG24) 1.5 (AWG16)
Main power 1.5 (AWG16) 2.5 (AWG12)
Protective grounding 1.5 (AWG16) 2.5 (AWG12)