Chapter 3. General Specifications
3-1
Chapter 3 General Specifications
3.1 General Specifications
The General specification of XGB series is as below.
No. Items Specifications
Related
standards
1
Ambient temperature
0 ~ 55 °C
-
2
Storage temperature
25 ~
+
70
°
C
3
Ambient humidity
5 ~ 95%RH (Non-condensing)
4
Storage humidity
5 ~ 95%RH (Non-condensing)
5 Vibration resistance
Occasional vibration
-
Frequency
Acceleration
Amplitude
times
IEC61131-2
5 f < 8.4Hz
3.5mm
10 times each
directions
(X, Y and Z)
8.4 f 150Hz
9.8m/s
2
(1G)
Continuous vibration
Frequency Acceleration
Pulse
width
5
f
<
8.4Hz
1.75mm
8.4
f
150Hz
4.9m/s
2
(0.5G)
6 Shock resistance
Peak acceleration: 147 m/s
2
(15G)
Duration: 11ms
Half-sine, 3 times each direction per each axis
7 Noise resistance
Square wave
Impulse noise
AC: ±1,500 V
DC:
±
900 V
LS ELECTRIC
standard
Electrostatic
discharge
4kV (Contact discharge)
IEC61131-2
IEC61000-4-2
Radiated
electromagnet
ic field noise
80 ~ 1,000 MHz, 10V/m
IEC61131-2,
IEC61000-4-3
Fast
transient/bust
noise
Segment
Power supply
module
Digital/analog input/output
communication interface
IEC61131-2
IEC61000-4-4
Voltage
2kV
1kV
8
Environment
Free from corrosive gasses and excessive dust
9
Altitude
Up to 2,000 ms
10
Pollution degree
2 or less
11
Cooling
Air-cooling
1) IEC (International Electrotechnical Commission)
: An international civil community that promotes international cooperation for standardization of electric/ electro
technology, publishes international standard and operates suitability assessment system related to the above.
2) Pollution Degree
: An index to indicate the pollution degree of used environment that determines the insulation performance of
the device. For example, pollution degree 2 means the state to occur the pollution of non-electric conductivity
generally, but the state to occur temporary electric conduction according to the formation of dew.