Document reference MAVM600MK2MPS-QS/E QUICK START MANUAL
Edition 2 - February 2021 VM600
Mk2
machinery protection system (MPS)
2-5
MPC4
Mk2
machinery protection and condition monitoring module
OVERVIEW OF VM600
Mk2
MACHINERY PROTECTION SYSTEM (MPS) HARDWARE
2.2.1 MPC4
Mk2
module LEDs
LEDs on the front panel of the MPC4
Mk2
module are used to indicate the status and
behaviour of a VM600
Mk2
MPS (MPC4
Mk2
+IOC4
Mk2
module and any associated RLC16
Mk2
modules).
In general:
The DIAG/STATUS LED indicates the status and behaviour of the VM600
Mk2
MPS:
DIAG/STATUS indicates system booting.
DIAG/STATUS indicates system not configured when blinking slowly.
DIAG/STATUS indicates normal system operation.
DIAG/STATUS indicates trip multiply when blinking slowly and alarm bypass
when blinking quickly.
DIAG/STATUS indicates fail safe (that is, the system-wide VM600
Mk2
MPS
safety-line control signal has been activated by the MPC4
Mk2
module).
•The CHn and AXn LEDs indicate the status and behaviour of the dynamic and auxiliary
channels respectively:
•CHn indicates channel not configured.
•CHn indicates normal channel operation.
•CHn indicates alarm bypass (AB) or sensor/measurement chain problem when on
continuously, an alert alarm (not first out) when blinking slowly and an alert
alarm (first out) when blinking quickly.
•CHn indicates a danger alarm (not first out) when blinking slowly and a danger
alarm (first out) when blinking quickly.
The LOCK LED indicates the status of the VM600
Mk2
MPS:
•LOCK indicates that the VM600
Mk2
MPS is Locked (safety/secure operating
mode).
•LOCK indicates that the VM600
Mk2
MPS is Unlocked (maintenance mode).
Table 2-1 provides detailed information on the behaviour of the MPC4
Mk2
LEDs when the
“standard” operating firmware is installed and running on the module.
Table 2-2 provides detailed information on the behaviour of the MPC4
Mk2
LEDs when the
recovery firmware is installed and running on the module.
Figure 2-2 provide some examples of MPC4
Mk2
LED activity for typical VM600
Mk2
MPS
situations.

Table of Contents

Other manuals for Meggitt vibro-meter VM600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Meggitt vibro-meter VM600 and is the answer not in the manual?

Meggitt vibro-meter VM600 Specifications

General IconGeneral
BrandMeggitt
Modelvibro-meter VM600
CategoryProtection Device
LanguageEnglish