Installation and Mounting
scanCONTROL 30xx
The multifunction socket can be used with either of the following configurations:
Configuration In1 In2 In3 In4
0 Encoder, positive edge of index
track
1
A B N
1 Encoder with external trigger input
1
Trigger A B N
2 External trigger input Trigger ppc 1
2
ppc 2 ppc 3
3 External trigger and load up to 8 user modes Trigger Bit 0 Bit 1 Bit 2
4 Load up to 15 user modes Bit 0 Bit 1 Bit 2 Bit 3
5 Insert into timestamp ppc 0 ppc 1 ppc 2 ppc 3
6 Frametrigger and encoder Start container A B Fill container
7 Frametrigger and encoderline A Start container A Fill container
8 Encoder with gate Gate A B N
9 External trigger, load up to 4 user modes and 1 input for timestamp Trigger Bit 0 Bit 1 ppc 3
10 Load up to 8 user modes and 1 input for timestamp Bit 0 Bit 1 Bit 2 ppc 3
11 Load up to 4 user modes and 2 inputs for timestamp Bit 0 Bit 1 ppc 2 ppc 3
Signal level (switching level):
The signal levels are switchable for all switching inputs together via software between LLL (TTL logic) and HLL (HTL):
- LLL level: Low 0 V… 0.8 V, High 2.4 V… 5 V, internal pull-up/down 10 kOhm to 5 V/GND
- HLL level: Low 0 V… 3 V, High 11 V… 24 V (permitted up to 30 V), internal pull-up/down 10 kOhm to 24 V/GND
- Pulse duration:
≥ 5 µs
i
Use a shielded cable with twisted wires, especially the recommended connection cable PCR3000-x from the accessories.
Connect the cable shield with the potential equalization PE or the connector housing.
1) The encoder input counts each edge. Encoder output typically 4 edges per encoder step.