2D/3D Output Unit
scanCONTROL 30xx
Connect the “System supply (out)“ terminals of the OU-Filter module to the “System supply (in)“
terminals of the OU-Fieldbus Coupler (0 V and 24 V, see Fig. 27).
Connect the system supply (in) of the OU-Filter module to the power supply (0 V and 24 V, see Fig. 27).
Connect the field supply (in) of the OU-Filter module to the power supply (0 V and 5 V/24 V, see Fig. 27).
i
The system supply and field supply should be separated to ensure the bus operation and electrical isolation in case of a short-
circuit of an actor.
7.3 Commissioning 2D/3D Output Unit
After having installed the required wiring of the modules of 2D/3D Output Unit, you have to parameterize the measurement system ac-
cording to your measurement task to get the desired signals at the digital and analog output ports.
Connect the sensor to the PC using the Ethernet cable.
Alternatively 2D/3D Output Unit can be connected simultaneously to the PC and to the sensor.
Parameterize the measurement system using scanCONTROL Configuration Tools and assign the desired signals to be output.
When the parameterization is finished, save the settings to a user mode of the sensor.
scanCONTROL Configuration Tools > Menu Parameters > Save parameters to scanCONTROL...
Refer to scanCONTROL Configuration Tools.
Exit scanCONTROL Configuration Tools and disconnect scanCONTROL 30xx, PC and if necessary
2D/3D Output Unit.
Connect the 2D/3D Output Unit by using the Ethernet cable.
scanCONTROL 30xx and the Output Unit operate now as an independent measurement system and the set signals are output via the
assigned ports.