4.5.1.1 Description/options
Setpoint is the variable that can be altered with this menu entry; 50% (example) is the currently set value of
this variable (in %RH).
Press Menu/Esc once more to leave the menu mode without changing any values.
indicates that you can move up the menu to go to the next menu entry by pressing Up. No changes will
be made to the setpoint value by doing so.
↵ indicates that this variable can be set by pressing ↵ Enter.
Press ↵ Enter to alter the value for Setpoint (possible range: 15-85%). The two digits resembling the value
on the display start to blink. Use the Up and Down buttons to make your changes, and confirm the new
value with ↵ Enter. The value will not be stored as long as you do not press this button.
4.5.2 Menu entry AlarmMax
With this entry you can define an upper threshold value for the humidity alarm to go off (master units only). If
the relative humidity inside the case rises beyond this value and if it remains there for at least 30 minutes
(standard alarm delay), an alarm will be issued from your EBC. Depending on the settings taken via the
menu entry for the first Alarm (see p. 30) the first humidity alarm can additionally be delayed for 1 to 99 days.
By default the AlarmMax value is usually stored 10 points above the value for the setpoint. The minimum
spacing required between AlarmMax and the setpoint is five points. Every time the setpoint is altered the
upper threshold value will be moved analogously to keep the same spacing that has been set before. If you
have, for instance, set an upper threshold value of 60% and you alter the setpoint from 50% to 55%, the
value for AlarmMax will be moved to 65% automatically. NOTE: If the setpoint is put to its highest possible
value (85%), the distance to AlarmMax is automatically reduced to 5 points, as otherwise the highest
possible value for AlarmMax (90%) would have been crossed. Once the difference came to rest at 5 points
by this it will be kept there - even if you chose a lower value for the setpoint shortly after. With a setpoint
chosen low enough, AlarmMax can of course be raised again manually, though.
Press Menu/Esc to call up the menu, then press Up once to move to the menu entry for the upper
threshold value (AlarmMax). The display reads:
Applies analogously to the individual products of series EBC10/11/12 (Rev.3). As of 24.11.2014. Subject
to modification.