4.5.11.1 Description/options
rH Corr is the variable that can be altered with this menu entry; -01% (example) is the currently set value of
this variable (in %RH). This value will be added to or subtracted from the read out value that comes in from
the RH/T sensor (i.e. 50%RH - 1%RH = 49%RH). Therefore, in the example the EBC will display and
consider 49% to be the current relative humidity during normal operation.
Press Menu/Esc once more to leave the menu mode without changing any values.
indicates that you can move up and down the menu to go to the next/previous menu entries by pressing
Up or Down.
indicates that this variable can be set by pressing Enter.
Press Enter to alter the value for rH Corr (possible range: -5 to +5%RH). The digits resembling the value
on the display start to blink. Use the Up or Down buttons to make your changes, and confirm the new
value with Enter. The value will not be stored as long as you do not press this button.
4.5.12 Menu entry Hyst.
With this entry you can set the value for the hysteresis (masters and slaves likewise). The hysteresis defines
a setpoint range around the setpoint chosen in menu entry 1. At a setpoint of i.e. 50% and a hysteresis of i.e.
2% the EBC will delay switching between its modes of operation (humidification, being in range,
dehumidification), so that for instance humidification will only start when the humidity level has fallen to 50-
2=48%. On the other hand, dehumidification would only start once the humidity level has reached
50+2=52%. Altogether, the hysteresis helps in flattening the curve for the relative air humidity inside the
case. As of Revision 2 all units out of series EBC10/11/12 offer this menu entry, enabling the user to choose
a value from 1 to 4% for the hysteresis, rather than to have this value being fixed at 2%, as it was the case
with all previous models of series EBC10/11/12. The factory-set value remains to be at "02%".
NOTE: Due to technical reasons the hysteresis has to be chosen for every single unit being part of a chain
of EBCs. So, changing the hysteresis on the master unit does not change the respective setting in any of the
slaves. Please do check the menu of all slaves, so that the different EBCs will not eventually work against
each other.
Press (one after the other on all EBCs, starting with the Master) Menu/Esc to call up the menu, then press
Up eleven times to move to the menu entry for the hysteresis (Hyst.). The display reads:
Applies analogously to the individual products of series EBC10/11/12 (Rev.3). As of 24.11.2014. Subject
to modification.