A l a r m B e e p O f f ↵
Fig. 15 - Display message in menu mode, 4th menu entry.
4.5.4.1 Description/options
AlarmBeep is the variable that can be altered with this menu entry; Off (example) is the currently set value of
this variable.
Press Menu/Esc once more to leave the menu mode without changing any values.
indicates that you can move up and down the menu to go to the next/previous menu entries by pressing
Up or Down. No changes will be made to the AlarmBeep value by doing so.
↵ indicates that this variable can be set by pressing ↵ Enter.
Press ↵ Enter to alter the value for AlarmBeep (possible values: Off, On). The letters resembling the value
on the display start to blink. Use the Up or Down buttons to make your changes, and confirm the new
value with ↵ Enter. The value will not be stored as long as you do not press this button.
4.5.5 Menu entry 1. Alarm
With this entry you define whether or not you want the EBC to delay its first humidity alarm (master units
only). This function is useful i.e. for newly installed systems or after the doors of the controlled case have
been opened for redecorations or the like. Default setting is "01D" (=one day, 24 hrs). At a set value of 00D
the first humidity alarm will be issued after the usual delay of 30 minutes. This minimum delay is always kept
for the EBCs to have some time for balancing the system air.
NOTE: If you intend to use this function and the EBC has possibly already issued a humidity alarm since it
was last pulled from the mains connection, you should now turn the EBC off, wait for the completion of the
possibly following pumping process, and then pull the mains plug. Wait for some minutes before plugging the
EBC back on. Then continue as intended.
Press Menu/Esc to call up the menu, then press Up four times to move to the menu entry for the delay of
the first humidity alarm (1. Alarm). The display reads:
1 . A l a r m 0 1 D ↵
Fig. 16 - Display message in menu mode, 5th menu entry.
Applies analogously to the individual products of series EBC10/11/12 (Rev.3). As of 24.11.2014. Subject
to modification.