miniClima Schönbauer GmbH
Brunner Str. 21b, 2700 WIENER NEUSTADT, AUSTRIA, EU
Tel. | Phone: +43 2622 24964, +43 6991 24964 01, Voicemail: +43 6993 24964 01, Fax: +43 2622 24964 15, E-Mail: office@miniclima.com
www.miniclima.com, twitter.com/miniClima, www.linkedin.com/company/miniclima-schönbauer-gmbh, www.google.com/+Miniclima, www.facebook.com/miniclima
UID | VAT-ID: ATU61994435, EORI: ATEOS1000001229, DVR: 4008782
Firmenbuchnummer | Trade Register Number: 267137z (Landesgericht | Regional Court of Wiener Neustadt)
Press Menu/Esc to call up the menu, then press Up nine times to move to the menu entry for the hours of
operation (OpHours). The display reads:
O p H o u r s 0 0 0 2 0 0
Fig. 21 - Display message in menu mode, 10th menu entry.
4.5.10.1 Description/options
OpHours is the variable that can be read out with this menu entry; 000200 (example) is the currently present
value of this variable (in hrs).
Press Menu/Esc once more to leave the menu mode.
indicates that you can move up and down the menu to go to the next/previous menu entries by pressing
Up or Down.
A missing ↵ symbol indicates that this is a read out menu entry, where no variables can be set.
4.5.11 Menu entry rH Corr
With this entry the EBC's interpretation of the data for the present RH value that is measured from the RH/T
sensor can be corrected (master units only). This function is required for calibrating the system in case a
metered (third party) instrument, which is positioned on the very same spot as the miniClima RH/T sensor,
provides clearly different values than the EBC does (via its display). Default setting is "+00%" (=no correction
of the signal).
NOTE: The value in the menu entry rH Corr can be altered on a slave unit, too, but this won't have any
effect as long as this EBC is used as a slave. Once the unit is plugged to a RH/T sensor (and thus becomes
a master), the EBC will use the last alteration for the interpretation of the incoming RH value, even if the
alteration has been made during slave mode. You can check and alter the setting at any time.
Press Menu/Esc to call up the menu, then press Up ten times to move to the menu entry for the correction
of the RH value as it is measured in the case (rH Corr). The display reads:
r H C o r r - 0 1 % ↵
Fig. 22 - Display message in menu mode, 11th menu entry.
Applies analogously to the individual products of series EBC10/11/12 (Rev.3). As of 24.11.2014. Subject
to modification.
miniClima - Manual_EBC10-11-12(Rev.3)_en