71
Panel Configuration/Features/Fire Drill
Fire Drill
[x] Enabled
This function is used to enable/disable fire drill operation from the fire common control fire drill
switch at the front panel.
Panel Configuration/Features/Waterflow Retard
Waterflow retard
[ ] Enabled
If disabled, all the initiating circuits configured as waterflow act as non-verified alarms. If enabled, retard
operation is performed for initiating circuits configured as waterflow.
Panel Configuration/Features/Auxiliary disconnect, disconnects alarm and supervisory relay
Aux Dis Alm&Sv
[ ] Enabled
If enabled the auxiliary disconnect operation, disconnects alarm and supervisory relays
disabled the auxiliary disconnect operation has no affect on the alarm and supervisory relays.
Default is disabled.
Panel Configuration/Features/Signal silence inhibit timer
Sig.sil. inh.
[x] Disabled
[ ] 10 sec
[ ] 20 sec
[ ] 30 sec
[ ] 1 min
Select the timer value for the signal silence inhibit timer.
Panel Configuration/Features/Auto signal silence timer
Auto sil. tmr
[x] Disabled
[ ] 5 min
[ ] 10 min
[ ] 15 min
[ ] 20 min
[ ] 30 min
Select timer value for the auto signal silence timer.
Panel Configuration/Features/Alarm transmit silence
Alm. xmit. sil.
[ ] Enabled
This feature allows the alarm transmits and auxiliary alarm relay to reset on “SIGNAL
SILENCE” rather than the “RESET” switch if enabled. Default is disabled.
Panel Configuration/Features/Power fail timer
Pwr fail tmr.
[x] None