72
[ ] 1 Hr
[ ] 2 Hrs
[ ] 3 Hrs
This feature allows a programmed delay before the AC fail trouble is transmitted by the
optional PR-300. (Note: the delay for transmission by the dialer is configured under Dialer
Configuration – Item 4 –Time Parameters - AC Loss Delay)
Panel Configuration/Features/Common supervisory relay
Com. supv. rly
[ ] Enabled
This feature is used to make the common supervisory relay acts as a common alarm relay if
enabled. Default is disabled
Panel Configuration/Features/Signal silence isolator
Sig. isolators
[ ] Enabled
This feature makes the system aware that the isolators are present on the main panel
powered output circuits if enabled. Default is disabled.
Panel Configuration/Features/Strobe types
Strobes type
[x] Normal
[ ] Gentex
[ ] System Sensor
[ ] Mircom
[ ] Wheelock
Select the strobe manufacturer for synchronous strobes. Synchronous strobes are driven by
following a different ON/OFF pattern depending on the manufacturer’s specification. Normal
means the strobes are not synchronized and when the circuit gets active it is turned ON
steady. This feature applies to the main panel powered output circuits, configured as strobes,
only.
Panel Configuration/Features/Evacuation code
Evac. Code
[ ] Continuous
[ ] March Time
[x] Temporal
[ ] California
Select the evacuation code for the 2nd stage in a two stage system and for the 1st stage in a
single stage system.
Panel Configuration/Features/Building alert
Bldg. alert
Note: Once a specific type of strobe is selected, for example Mircom, then only this type
of strobe is allowed for the entire system.