EasyManuals Logo

Mircom FX-400 User Manual

Mircom FX-400
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #73 background imageLoading...
Page #73 background image
73
[ ] Enabled
Alert sounds for building input activation. Default is disabled.
Panel Configuration/Features/Device LED flashing
Dev. Flash
[ ] Enabled
This feature allows flashing of the LED on the addressable sensors to flash momentarily, while
polling, if enabled. The input and output modules LED always flashes, while polling,
regardless of this feature enabled or disabled.
Panel Configuration/Features/Class-A loop
Loop ClassA
[ ] Enabled
This feature configures all addressable loops as Class A if enabled.
Panel Configuration/Features/Auto after hours
Auto afthrs.
[ ] Enabled
This feature allows the daytime/nighttime mode to be set automatically if enabled.
Panel Configuration/Features/General alarm timer
Gen.alm tmr
[x] Disabled
[ ] 5 min
[ ] 10 min
[ ] 15 min
[ ] 20 min
[ ] 30 min
This feature sets the value for the general alarm timer
Panel Configuration/Features/Common alarm relay operation
This section is reserved for future use.
Panel Configuration/Features/Agency selection
Jurisdiction
[x] ULI
[ ] ULC
Default is ULI. This feature selects the agency having jurisdiction for the panel.
PANEL CONFIGURATION/2. ADDRESS CFG.
This section is reserved for future use.
PANEL CONFIGURATION/3. DEVICE LABEL
Allows the user to edit the device label. Device Address Prompt:
Device address:
Loop: _ DevAddr:___

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom FX-400 and is the answer not in the manual?

Mircom FX-400 Specifications

General IconGeneral
BrandMircom
ModelFX-400
CategoryControl Panel
LanguageEnglish

Related product manuals