Built-in Positioning Functions
2 Specifications
2.5 Output Specifications
B - 37
A
Common Items
B
Built-in
Positioning
Functions
Apx.
Example
Connection
2.5.5 FX3UC Series main unit (Transistor Output)
This section describes the transistor output specifications of the FX3UC Series main unit. Note that the
simultaneous turning-on rate is restricted for the output extension units and the main unit. For details on this
restriction, refer to the following manual:
Refer to the FX
3UC Hardware Edition.
For MELSERVO Series amplifiers, use a sink input/sink output type PLC.
*1. When the two COM1 terminals are connected outside the PLC, resistance load is 1.6 A or less.
*2. The FX
3UC-32MT-LT(-2) uses the display module for monitoring.
Pulse output terminals Y000, Y001, and Y002 are high-speed response output terminals.
To use the positioning instruction, adjust the load current of the NPN open collector to 10 to 100 mA (5 to 24 V DC)
.
1. Sink internal output circuit
*3. To ground the unit, refer to the servo amplifier (drive unit) manual. If the grounding method is not
specified, carry out class-D grounding.
Item Transistor output specifications
External voltage All outputs 5 to 30 V DC
Maximum
load
Resistance load
Y000 to Y003 0.3 A/point The total load current of the common
items (8 points) should be 0.8 A
*1
or
less.
Y004 or more 0.1 A/1point
Inductive load
Y000 to Y003
7.2 W/1point
(24 V DC)
The total load of the common items
(16 points) should be 38.4 W or less at
24 V DC.
Y004 or more
2.4 W/1point
(24 V DC)
Open-circuit leakage current All outputs 0.1 mA or less at 30 V DC
ON voltage All outputs 1.5 V or less
Response
time
FX
3UC-32MT-LT
FX
3UC-32MT-LT-2
OFFON
ONOFF
Y000 to Y003 5 s or less at 10 mA or more (5 to 24 V DC)
Y004 to Y017 0.2 ms or less at 100 mA (at 24 V DC)
FX
3UC-MT/D
FX
3UC-MT/DSS
OFFON
ONOFF
Y000 to Y002 5 s or less at 10 mA or more (5 to 24 V DC)
Y003 or more 0.2 ms or less at 100 mA (at 24 V DC)
Circuit insulation All outputs Photocoupler insulation
Indication of output motion All outputs
LED is lit when the photocoupler is driven.
*2
Item Description
Operation voltage range 5 to 24 V DC
Operation current range 10 to 100 mA
Output frequency 100 kHz or less
Y0
Y4
FX3UC- MT/D
FX
3UC-32MT-LT(-2)
Main unit
Grounding
*3
Servo amplifier
(Drive unit)
Pulse train signal
Direction signal
5 to 24 V DC
COM1