25
6.2.5. Measure against noise
Because of the measure against the noise, please peel the sheath of the CC-Link cable, and the
ground clamp of the metal braid section at the case, and mount the ferrite core (recommendation
article: E04SR301334 * SEIWA ELECTRIC MFG.) on less than 30cm from the clamp position.
The connection method by controller is shown in the following.
(1) CR800-D controller
Figure 6.2-4 Connection of the CC-Link cable (CR800-D controller)
(2) CR750-D/CR751-D controller
Figure 6.2-5 Connection of the CC-Link cable (CR750-D/CR751-D controller)
<CR800-D controller front>
ーブアース
(アース)
CC-Linkブル
(客様準備)
ェラトコ
(付属品)
CC-Link cable
(Customer preparation)
Cable ground clamp
position *1
(Ground clamp
attachments)
Ferrite core
(attachments
ルアクラ位置
(ラン付属品)
ルアクラ位置
(ラン付属品)
CC-Linkケー
(お客準備)
(付属品)
CC-Linkケー
(お客準備)
(付属品)
<CR750-D controller rear>
<CR751-D controller front >
CC-Link cable
(Customer preparation)
Cable ground clamp
position *1
(Ground clamp
attachments)
Ferrite core
(attachments
Cable ground clamp
position *1
(Ground clamp
attachments)
Ferrite core
(attachments
CC-Link cable
(Customer preparation)