1 FUNCTIONS
1.5 Scaling Function
29
1
When 32000 is set to the scaling upper limit value and -32000 is set to the scaling lower limit value for the module with the
input range of 4 to 20mA (extended mode)
*1 Because the value falls below the range of -32768 to 32767, the value is fixed to -32768 (the lower limit value).
*2 Because the value exceeds the range of -32768 to 32767, the value is fixed to 32767 (the upper limit value).
When the scaling function is used with the digital clipping function, the scale conversion is performed on the
digital operation values after digital clipping.
Current input (mA) Digital output value Digital operation value
(scaling value)
16 bits 32 bits
0 -8000 -8000 -32768
*1
4 0 0 -32000
8 8000 8000 -16000
12 16000 16000 0
16 24000 24000 16000
20 32000 32000 32000
20.24 32480 32480 32767
*2
22 32767
*2
36000 32767
*2
32000
36000
0
-8000
20 2204
Analog input current (mA)
Scaling upper limit value: 32000
Scaling lower limit value: -32000