NICE5000 User Manual 7 Description of Function Codes
- 155 -
Bit Function Description Default
Bit15
Higher/Low voltage
1.5s time detection
This function can be enabled when both higher voltage
and low voltage detections are performed on the door
lock circuit or safety circuit. When the time interval
between higher voltage and low voltage detection
exceeds 1.5s, the controller reports the door lock fault.
0
F6-11 Elevator function selection 3
Bit0
Fire emergency
display
There is hall call display after the elevator enters the re
emergency state and returns to the re emergency oor.
0
Bit1
Fireghter operation
display
There is hall call display when the elevator is in
reghter operation state.
0
Bit2
Direction display at
micro-leveling
The adjustment direction is displayed during micro-
leveling adjustment.
0
Bit3
Determined direction
display in attendant
state
The determined direction is displayed at stop in
attendant state, even if there is no call.
0
Bit4
No direction display
at automatic stop
There is no direction display at automatic stop.
0
Bit5
Elevator lock at door
open
In the elevator lock state, the elevator keeps the door
open at the elevator lock oor.
0
Bit6
Display available at
elevator lock
In the elevator lock state, hall calls are displayed
normally.
0
Bit7
Elevator lock at any
oor hall call
The system enters the elevator lock state or returns to
the re emergency oor at a hall call from any oor.
0
Bit8
Clear oor number
in advance
The displayed floor number is cleared before the
elevator reaches the destination oor.
0
Bit9
Clear oor number in
advance in attendant
state
The displayed floor number is cleared before the
elevator reaches the destination floor in attendant
running state.
Bit10
Displaying next
arriving oor number
The next floor to be arrived at is displayed during
elevator running.
0
Bit11 Blinking at arrival
The car display blinks when the elevator arrives at a
oor. The blinking advance time is set in F6-12.
0
Bit12
Door re-open during
door open delay
The door re-opens if the door open delay input is active
during door close.
0
Bit13
Door re-open after
car call of the
present oor
The door re-opens if the car call of the present oor is
valid during door close.
0
Bit14
Door re-open at door
close limit
The door re-opens if the door open signal is active at
door close limit.
0
Bit15 Reserved
- 0
Function Code Parameter Name Setting Range Default Unit Property
F6-12
Blinking advance time 0.0–15.0
2.0 s

Table of Contents