7 Description of Function Codes NICE5000 User Manual
- 156 -
It is used to set the blinking advance time when the elevator arrives the oor required by the
car call.
Function Code Parameter Name Setting Range Default Unit Property
F6-13
Parking oor 2 start time 00.00–23.59
0 - ★
F6-14
Parking oor 2 end time 00.00–23.59
0 - ★
F6-15
Parking oor 2 0 to F6-00
0 - ★
The elevator returns to the oor set in F6-15 if idle during the time period set in F6-13 to F6-
14.
Parking oor 2 can also be enabled by using the parking oor switchover switch.
Function Code Parameter Name Setting Range Default Unit Property
F6-16
Fire emergency oor 2 0 to F6-00
0 - ★
Fire emergency oor 2 set in this parameter is enabled by using the re emergency oor
switchover switch.
Function Code Parameter Name Setting Range Default Unit Property
F6-17
Fire emergency function
selection 1
0–65535
1283 - ★
F6-18
Fire emergency function
selection 2
0–65535
1291 - ★
F6-19
Fire emergency function
selection 3
0–65535
17156 - ★
These parameters are used to select the required re emergency functions. Each bit of the
function code denes a function, as described in the following table.
If a bit is set to 1, the function indicated by this bit is enabled; if this bit is set to 0, the
function is disabled.
The functions dened by the binary bits are described in the following table.
Bit Function Description Default
F6-17 Fire emergency function selection 1
Bit0
Fire emergency 1
door 1 valid
In re emergency state, the elevator under opposite door
control opens the corresponding door.
1
Bit1
Fire emergency 1
door 2 valid
1
Bit2
Nearest oor for
re emergency
The elevator arrives at the nearest landing oor and uses
it as the re emergency oor.
0
Bit3
Opposite
door control
unchanged
Opposite door control in re emergency state is the same
as that during normal running
0