NICE5000 User Manual 7 Description of Function Codes
- 157 -
Bit Function Description Default
Bit4 Reserved
- 0
Bit5
Retentive at
power failure
In re emergency state, the controller records the system
and current car states at power failure and restores these
state after power-on again.
0
Bit6 to
Bit7
Reserved
- 0
Bit8
Fire emergency
indicator blinking
at re emergency
1
These functions control the re emergency indicator and
tone in re emergency state.
The following conditions are required to implement the
functions:
Install the HCB-B.
Set the functions of the HCB-B output terminals in group
FL parameters.
Connect the re emergency components to the
corresponding output terminals.
1
Bit9
Fire emergency
indicator steady
ON at re
emergency 1
0
Bit10
Fire emergency
tone
discontinuous
prompt at re
emergency 1
1
F6-18 Fire emergency function selection 2
Bit0
Fire emergency 2
door 1 valid
In reghter operation state, the elevator under opposite
door control opens the corresponding door.
1
Bit1
Fire emergency
2door 2 valid
1
Bit2
Entering
reghter
operation state
automatically
Upon door open limit after the elevator returns to the re
emergency oor, the elevator automatically enters the
reghter operation state.
0
Bit3 Fireghter switch
Upon door open limit after the elevator returns to the
re emergency oor, the elevator enters the reghter
operation state only after the reghter switch input inside
the car is active.
1
Bit4
Fire emergency
switch switchover
After the re emergency switch is active, the elevator
returns to the re emergency oor and opens the door.
Then, the re emergency switch becomes inactive and
active again (within 500 ms), the elevator enters the
reghter operation state.
0
Bit5 to
Bit6
Reserved
- 0
Bit7
Low speed door
close
It is used to implement low speed door close in re
emergency state.
0