Set the required pressure, according to the air flow specification. The greater the difference between the
exterior and interior pressures, the great the air flow.
•
Static Pressure in Minimum Ventilation or Extra Ventilation
•
Static Pressure Main Screen
•
Static Pressure Settings Screen
•
High Static Pressure Alarm State
12.2.3.2.1 Static Pressure in Minimum Ventilation or Extra Ventilation
In minimum/extra ventilation the target pressure is adjusted as a function of the outside temperature. TRIO
calculates the pressure target according to a curve between low and high temperature target pressure set-
points.
The curve is adjusted according to the outside temperature, in order to maintain the pressure. If the
outside temperature is warm, large amounts of slow moving air is allowed to enter the house (low static
pressure). When the outside air is cold, the Vent Master adjusts the inlets to allow a low volume of fast-
moving cold air (high static pressure).
NOTE
Version 4.1.6 supports opening the vents at 0% ventilation.
12.2.3.2.2 Static Pressure Main Screen
1. Go to Climate > Static Pressure.