© Munters AB, 2020 131
12.4.2 D
EFINING THE
T
UNNEL
V
ENTILATION
S
ETTINGS
Define:
o
Tunnel Hysteresis: This is a differential. When the temperature reaches the tunnel
temperature minus this differential, ventilation goes down to Extra Ventilation (if enabled)
or Minimum Ventilation.
o
Outside Temp Exit Limit: This is a differential. When the outside temperature reaches the
tunnel temperature plus this differential, ventilation will remain in Tunnel Mode.
o
Tunnel Exit Delay (min.): When TRIO calculates that ventilation should exit Tunnel Mode,
there is a delay (of this amount of time) before actually exiting. This parameter prevents
TRIO from entering and exiting Tunnel Mode too rapidly.
12.4.3
T
UNNEL
D
OORS
In Tunnel Ventilation, TRIO enables control over the tunnel doors using control by level or control by
static pressure. Control of these doors is the same as control over inlets. Refer to these sections for details.
Inlet and Curtain Ventilation

Table of Contents

Other manuals for Munters Trio Poultry Controller

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Munters Trio Poultry Controller and is the answer not in the manual?

Munters Trio Poultry Controller Specifications

General IconGeneral
BrandMunters
ModelTrio Poultry Controller
CategoryController
LanguageEnglish

Related product manuals