© Munters AB, 2020 130
3. Go to Climate > Ventilation and click the Tunnel Tab.
4. On each level, define:
o
Level: Read-only.
o
Diff T: Define the temperature differential. When the temperature rises above the target
temperature by this amount at each level, Extra Ventilation begins. Range: 0.0°C
>10.0°C.
NOTE
Each differential must be equal to or higher than the previous level’s differential.
o
Fan Status. Refer to Defining Basic Ventilation, page 116 on how to configure fans.