© Munters AB, 2020 129
o
Level: Read-only.
o
Diff T: Define the temperature differential. When the temperature rises above the target
temperature by this amount at each level, Extra Ventilation begins. Range: 0.0°C
>10.0°C.
NOTE
Each differential must be equal to or higher than the previous level’s differential.
o
Fan Status. Refer to Defining Basic Ventilation, page 116 on how to configure fans.
12.4 Tunnel Ventilation
When enabled, you can:
•
Set Tunnel levels in the ventilation program.
•
Define tunnel set points in the ventilation program.
•
Define Pressure settings for tunnel.
•
Define Tunnel temperature set point in the temperature curve (refer to Configuring the
Temperature Curve, page 103).
One tunnel door must be mapped or tunnel ventilation will not operate.
Configuring Tunnel Ventilation requires mapping at least one fan or one tunnel door.
Tunnel Ventilation must be enabled for the functions to appear on the screen.
•
Defining the Tunnel Ventilation
•
Defining the Tunnel Ventilation Settings
•
Tunnel Doors
•
Defining the Wind Chill Factor
12.4.1 D
EFINING THE
T
UNNEL
V
ENTILATION
P
ARAMETERS
1. Go to System > Control Strategy > Ventilation .
2. Under Ventilation, enable Tunnel.