EasyManua.ls Logo

Myron L 750 II Series - Pa Piezo Alarm; Description; Installation

Myron L 750 II Series
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
48
I. PIEZO ELECTRIC ALARM
-PA Piezo Electric Alarm ordered with Digital
Monitor/controller.
PAO Piezo Electric Alarm ordered separately for Digital or
remotely mounted Analog Monitor/controller or OEM
models.
1. DESCRIPTION
The PA/PAO is an electronic sound device capable of emitting a
80dBormore@30cm,highpitchedsqueal.SeegureIII.I.1.
Specications
OscillatingFrequency—3.0≠0.5KHz
OperatingVoltage(750II)—24VDCNom.(1.5-30VDCMax.)
SoundPressureLevel(Min)30cm/12VDC—80dB
Currentconsumption(Max)@12VDC—12mA
Tone — Constant
OperatingTemperature—-20-+60°C
Size — 24 x 9.5 mm
2. INSTALLATION
Briey-
The PA/PAO Piezo Alarm attaches to the front panel with the
tapesupplied,seegureIII.I.3.
The wire harness plugs into a methode connector on the main
CB*,seegureIII.I.4.
*MayalsobeconnectedtotheSCModuleasshowningure
III.I.5, if desired or so equipped.
WARNING: BEFORE STARTING, IF MONITOR/
CONTROLLER IS INSTALLED, ENSURE THE POWER IS OFF.
FAILURE TO DO SO COULD CAUSE DAMAGE TO THE IN-
STRUMENT, AND COULD BE HARMFUL OR FATAL TO PER-
SONNEL. ONLY QUALIFIED PERSONNEL SHOULD INSTALL
OR SERVICE ELECTRICAL EQUIPMENT.
Physical
NOTE: Remote mounting will require a .25” (6.35mm) hole, and
extending the harness. Use #22 gauge speaker wire. Observe
polarity.
If the front panel has all ready been removed from the enclosure
skip to #4.
1. Using a standard slot screwdriver remove the four (4)
screws on the front panel.
2. Carefully wiggle the front panel to loosen.
Pull gently toward you. Do not pull more
than about 8 inches/20CM or you could damage the
wiring harness.
3. Turn the front panel around so that the back side is
facing you.
4. Using a 1/4” drill or a sharp knife, carefully open the
CENTER front hole in the front panel as shown in
gureIII.I.2.
5. Peal off tape backing from PA, and install between
guidesasshowningureIII.I.3.
6. Set front panel aside.
7. Connect wire harness to Main CB as shown in
gureIII.I.4,ortoSCasshowningureIII.I.5.
Test
1. Turn power ON.Dependingonconguration,thePiezo
will sound off when —.
NOTE: If the sensor is connected, the solution value, set point
value and Set Point Conversion (SPC) jumpers may affect the
test.
a. For a Conductivity/TDS Monitor/controller, as
shipped from the Myron L
®
Company, the alarm
will
CAUTION - READ FOLLOWING CAREFULLY
Figure III.I.1
Double Backed Tape
Harness ~12"
Piezo Alarm
Methode Connector
Figure III.I.2
FRONT PANEL
Rear View
CUT OPEN
THIS HOLE

Table of Contents

Related product manuals