EasyManua.ls Logo

NAiS FP2 - Connection Example of PLC Link; When Using Three Plcs

NAiS FP2
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-13
5.4 Connection Examp le of PLC Link
5.4.1
When using three PLCs
The following example demonstrates how the PLC can be connected to two other FPΣ PLCs using a
PLC link connection. In the example shown here, link relays are use. When X1 of control unit no. 1 turns
on, Y0 of unit no. 2 turns on. When X2 of unit no. 1 turns on, Y0 of unit no. 3 turns on.
System register settings
When using a PC(PLC) link, the settings are fixed as below. (The settings using the memory
switch are ignored.)
Setting Setting value
Baud rate 115200 bps
Character bit 8 bits
Parity Odd
Stop bit 1 bit
RS/CS (Only when using RS232C) Invalid
Send waiting time 0.00 ms
Header STX not exist
Terminator CR
Initialize modem No
Unit no. and communication mode settings
- Setting for FPΣ
ΣΣ
Σ of unit no. 1
Name Set value
COM port 1 unit no. 1 (setting using the unit no. setting switch)
COM port 1 communication mode PC(PLC) link (system register No. 412)
- Setting for FP2 of unit no. 2
Name Set value
COM port 1 unit no. 2 (setting using the unit no. setting switch)
COM port 1 communication mode PC(PLC) link (using the mode speed setting switch)
- Setting for FP2SH of unit no. 3
Name Set value
COM port 1 unit no. 3 (setting using the unit no. setting switch)
COM port 1 communication mode PC(PLC) link (using the mode speed setting switch)
Key Point:
Make sure the same unit number is not used for more than one of the PLCs connected through the
PC(PLC) link function.
The method of some settings for FP2/FP2SH is different from the method for FPΣ.
Reference: For the details on PC(PLC) link of FPΣ, refer to <FPΣ User’s Manual ARCT1F333>.

Table of Contents

Related product manuals