6-11
Key Point:
Do not include the terminator in the transmission data. The terminator is added automatically.
When “STX exist” is specified for the header, do not add the header to the transmission data. The
header is added automatically.
When using the communication block (AFP2803 RS232C type) and setting the RS/CS to be valide,
transmission does not take place until CS (Clear to Send) turns on. If you are not going to connect to
the other device, set the RS/CS to be invalid.
The maximum number of transmission bytes “n” is 2048. (However, the header and terminator are
included.) When using the header and terminator subtract the byte numbers for them.
The contact numbers in parentheses refer to COM port 2.
Reference: <9.2 Appendix (Time Chart)>
Note: Followings can be set using F159 (MTRN) as well as the data transmission.
1. Switching the applications of COM port.
2. Communication conditions.
Reference: <Capter 8 Applications) > <9.6 F159 (MTRN)/F161 (MRCV) instructions>