Doc# E107706 2 - 7
2: Meter Overview
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
6. Default web pages with an extensive array of readings come with the meter. The
content of the pages can be customized using FTP Client. Follow these steps:
a. Click the Advanced Settings button in the Communications Settings screen.
b. Click the FTP Client tab on the top of the Advanced Settings screen. Using FTP,
you can easily replace any file by using the same file name as the one you want
to replace.
c. Click OK.
7. Enter the Email Server IP Address. The Default Settings store one Email Server IP
Address for administrative purposes or to send an alarm, if there is a problem. An
additional 8 email addresses can be configured with FTP Client.
8. Update Firmware, if necessary, with TFTP protocol (see Appendix C).
9. After the parameters are configured, Communicator EXT
TM
software connects via
the Network using a Device Address of “1” and the assigned IP Address when you
follow these steps:
a. Open Communicator EXT
TM
software.
b. Click the Connect icon in the Icon tool bar to open the Connect screen.
c. Click the Network button at the top of the screen and then enter the following
information:
• Device Address:1
• Host: IP Address (per your network administrator). Example: 10.0.0.1
• Network Port: 502
• Protocol: Modbus TCP
d. Click the Connect button at the bottom of the screen. The Communicator EXT
TM
software connects to the meter via the Network settings you entered.