EasyManua.ls Logo

Nexus 1250 - Linking Multiple Nexus Meters in Series

Nexus 1250
186 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Doc# E107706 5 - 13
5: Communication Wiring
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
5.7: Linking Multiple Nexus® Meters in Series
You may connect a total of 31 Nexus® meters in series on a single bus using RS485.
The cable length may not exceed 4000 feet (1219 meters). Before assembling the
bus, each Nexus® meter must be assigned a unique address. See Chapter 13 in the
Communicator EXT
TM
4.0 and MeterManager EXT Software User Manual for instruc-
tions.
• Connect the + and - terminals of each Nexus® meter. Use jumpers on any RS485
Master connected at the end of the chain.
• Connect the shield to the (S) terminal on each Nexus® meter and to the Ground on
the RS485 Master. This connection is used to reference the Nexus® meter’s port to
the same potential as the source. It is not an earth-ground connection. You must
also connect the shield to earth-ground at one point. Vous devez égale-
ment connecter l’écran à la terre à un moment donné.
• Provide termination resistors at each end, connected to the (+) and (-) lines. RT is
approximately 120 Ohms, but this value may vary based on length of cable run,
gauge or the impedance of the wire. See RT EXPLANATION in Section 5.3 .
Figure 5.9: Linking Multiple Nexus® Meters in Series
Table 2:
Nexus® Display VA Ratings
P41N+/P41N+/
P43N+
LED Displays 8VA
Twisted pair, shielded (SH) cable
R
T
+ - SH
R
T
+ - SH
+ - SH
+ - SH
Slave device 1
Slave device 2
Last Slave device N Master device
Earth Connection, preferably at
single location
Twisted pair, shielded (SH) cable Twisted pair, shielded (SH) cable

Table of Contents

Related product manuals