5 Parameter
BU 0800 en-4521 105
P551 Drive profile S
Setting range
0 … 3
Factory setting
{ 0 }
Description
Activation of a process data profile.
Setting values
Value Meaning
0 USS No specific drive profile.
1
CANopen DS402
CANopen drive profile according to DS402.
2
Reserve
3 Nord-Custom Drive profile with freely assignable bits.
Note: The free bits are set via parameters P480 / P481
P553 PLC set values
Setting range
0 … 57
Arrays
[-01] =
PLC setpoint 1
[-02] =
PLC setpoint 2
[-03] =
PLC setpoint 3
[-04] =
PLC setpoint 4
[-05] =
PLC setpoint 5
Factory setting
All { 0 }
Description
Assignment of functions for the various PLC control bits.
Note
Condition:
P350 = 1
and
P351 = 0
or
1
.
Setting values
Value Meaning Value Meaning
P554 Min. chopper Chop. S
Setting range
65 … 102 %
Factory setting
{ 65 }
Description
"Minimum chopper threshold". Adjustment of the switching threshold of the brake
chopper.
Note
An increase in this setting leads to a faster overvoltage FI switch off.
For applications where pulsating energy is returned (crank drives) the braking resistor
power dissipation can be minimised by increasing this setting.
In case of an FI error the brake chopper is generally disabled.
Setting values
Value Meaning
65 ...
100
Brake chopper switching threshold.
101
In case of an FI error the brake chopper is always disabled. Monitoring is also active if the FI is not
enabled. Chopper activation at 65%, e.g. in the event of an increase in the link circuit voltage due to a
mains fault.
102
Chopper always switched on, except for active chopper overcurrent (error E003.4).