Operating Parameters
B-17
Part 1126931_01
2018 Nordson Corporation
65 Schedule 3 Heaters On
Description:
Used to set the time that the clock will turn on the heaters during schedule 3.
Value:
0000 to 2359, ‐ ‐ ‐ ‐
Resolution:
1 minute
Default Value:
‐ ‐ ‐ ‐
Format:
Hours, Hour: Minute, Minute
Use:
Set the desired time for the heaters to turn on.
To disable this parameter, set the parameter's value to “‐ ‐ ‐ ‐” by simultaneously
pressing both of the right‐display scroll keys.
66 Schedule 3 Heaters Off
Description:
Used to set the time that the clock will turn off the heaters during schedule 3.
Value:
0000 to 2359, ‐ ‐ ‐ ‐
Resolution:
1 minute
Default Value:
‐ ‐ ‐ ‐
Format:
Hours, Hour: Minute, Minute
Use:
To disable this parameter, set the parameter's value to “‐ ‐ ‐ ‐” by simultaneously
pressing both of the right‐display scroll keys.
67 Schedule 3 Enter Standby
Description:
Used to set the time that the melter will enter the standby mode during schedule
3.
Value:
0000 to 2359, ‐ ‐ ‐ ‐
Resolution:
1 minute
Default Value:
‐ ‐ ‐ ‐
Format:
Hour, Hour: Minute, Minute
Use:
Set the time that the melter will enter the standby mode during schedule 3.
To disable this parameter, set the parameter's value to “‐ ‐ ‐ ‐” by simultaneously
pressing both of the right‐display scroll keys.
Note: Do not set an enter standby time that is outside of the time period defined
by the schedule's heater on and off time. The melter cannot enter the standby
mode when the heaters are off.