Operating Parameters
B-18
Part 1126931_01
2018 Nordson Corporation
Seven‐day Clock (contd)
68 Schedule 3 Exit Standby
Description:
Used to set the time that the melter will exit the standby mode during schedule 3.
Value:
0000 to 2359, ‐ ‐ ‐ ‐
Resolution:
1 minute
Default Value:
‐ ‐ ‐ ‐
Format:
Hour, Hour: Minute, Minute
Use:
Set the time that the melter will exit the standby mode during schedule 3.
To disable this parameter, set the parameter's value to “‐ ‐ ‐ ‐” by simultaneously
pressing both of the right‐display scroll keys.
Note: Do not set an exit standby time that is outside of the time period defined
by the schedule's heater on and off time. The melter cannot enter the standby
mode when the heaters are off.
71-
77
Schedules for the Days of the Week
Description:
Used to select which schedule(s) should be used on a specific day of
the week.
Value:
0 – Remain at last clock transition
1 – Use just schedule 1
2 – Use just schedule 2
3 – Use just schedule 3
4 – Use schedule 1 and 2
5 – Use schedule 2 and 3
6 – Use schedule 1 and 3
7 – Use schedule 1, 2, and 3
Resolution:
1
Default Value:
0
Format:
Use:
Selects the active schedule(s) for the day.
NOTES: If the 0 schedule option is used, the heaters will not turn on
again until the next scheduled heaters on time arrives.