ARYAL S2 E DUAL / TRIAL
ENGLISH
EN - 15
7.2.1 - Specications
Specifications

Specifications
Number of units that can be used
together
Connected units
1-5 units
Compressor stop/start frequency Stop time 3 min or more
voltage uctuation ±10% of rated voltage
Power source voltage
voltage drop during start ±15% of rated voltage
interval unbalance ±3% of rated voltage
Unit: m
10m(32.8ft)
When installing multiple indoor units with a single outdoor unit, ensure that the length of the
refrigerant pipe and the drop height between the indoor and outdoor units meet the requirements
illustrated in the following diagram:
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
15m(49ft)
15m(49ft)
Max.Height dierence
Dual
Trial
Max. length for all rooms 40 60
Max. length for one indoor unit 25 30
Max. height dierent between indoor and outdoor unit
15 15
Max. height dierent between indoor units 10 10
NOTE: For the units adopt quick connectors, no more than two pipes can be connected, and the Max.
length for each pipe is 7.5 meters.
Specifications

Specifications
Number of units that can be used
together
Connected units
1-5 units
Compressor stop/start frequency Stop time 3 min or more
voltage uctuation ±10% of rated voltage
Power source voltage
voltage drop during start ±15% of rated voltage
interval unbalance ±3% of rated voltage
Unit: m
10m(32.8ft)
When installing multiple indoor units with a single outdoor unit, ensure that the length of the
refrigerant pipe and the drop height between the indoor and outdoor units meet the requirements
illustrated in the following diagram:
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
15m(49ft)
15m(49ft)
Max.Height dierence
Dual
Trial
Max. length for all rooms 40 60
Max. length for one indoor unit 25 30
Max. height dierent between indoor and outdoor unit
15 15
Max. height dierent between indoor units 10 10
NOTE: For the units adopt quick connectors, no more than two pipes can be connected, and the Max.
length for each pipe is 7.5 meters.
Fortheunitsadoptquickconnectors,nomorethantwopipescanbeconnected,andtheMax.
length for each pipe is 7.5 meters.
When installing multiple indoor units with a single outdoor unit, ensure that the length of the refrigerant pipe
and the drop height between the indoor and outdoor units meet the requirements illustrated in the following
diagram: