A
A-4 CP1L Programming Examples
SYSMAC CP1L Getting Started Guide 129
Appendix
zTime Comparison Instructions
Time comparison instructions allow for easy comparisons of time.
E.g. If 0.00 is ON and the time is 13:00:00, turn 100.00 ON.
The hour, minute, and second of the current time in the CPU unit's built-in
clock (A351 to A352) and set time (D100 to D102) will be compared.
- - 1 1 1 0 0 0
D100
=DT
D0
A351
100.00
0.00
S2
C
S1
Set D0=0038Hex
7 6 5 4 3 2 1 0
D0
Compare seconds
Mask years
Mask months
Mask days
Compare hours
Compare minutes
Compare highlighted data
351
353
352
15 9 7 0
Minute
Year
S2 :D100
S2+2:D102
S2+1:D101
15 9 7 0
00 00
- -
- 13
Reflected on condition flag when power is turned ON
Hour
Day
Second
Month
W07E-EN-02+CP1L+GettingStartedGuide.book Seite 129 Montag, 15. September 2008 11:15 11