140
Analog I/O Terminals Section 4-8
The following table summarizes the DIP switch settings. (All pins are factory-
set to OFF.)
* Factory settings.
Note Always turn OFF the Slave’s power supply (including the communications
power supply) before changing any settings.
Rotary Switch Setting Set the input signal range for each input with the rotary switch. Inputs 0 and 2
share the same signal range, as do inputs 1 and 3.
The voltage input/current input selection is carried out by connecting the V+
terminal to the I+ terminal. Short-circuit the V+ terminal and I+ terminal when
inputting current.
Note Always turn OFF the Slave’s power supply (including the communications
power supply) before changing any settings.
DRT1-AD04
The following table shows the rotary switch settings and corresponding input
signal range settings.
Pin(s) Function Settings Setting contents
DRT1-AD04 DRT1-AD04H
1 through
6
Node address set-
ting
Refer to 4-8-1 Node Address and Baud Rate Set-
ting for details. (Factory-set to OFF.)
7 and 8 Baud rate
9 Number of inputs
setting (2 or 4)
(See page 146 for
details.)
OFF* 4 points Not used. (Must
be OFF.)
ON 2 points
10 Averaging function
(See page 147 for
details.)
OFF* Averaging is not
performed. (Fac-
tory setting)
Not used. (Must
be OFF.)
ON Averaging is per-
formed.
No. Signal range for inputs 0 and 2 Signal range for inputs 1 and 3
0 0 to 5 V or 0 to 20 mA 0 to 5 V or 0 to 20 mA
1 0 to 5 V or 0 to 20 mA 1 to 5 V or 4 to 20 mA
2 0 to 5 V or 0 to 20 mA 0 to 10 V
3 0 to 5 V or 0 to 20 mA –10 to +10 V
4 1 to 5 V or 4 to 20 mA 1 to 5 V or 4 to 20 mA
5 1 to 5 V or 4 to 20 mA 0 to 10 V
6 1 to 5 V or 4 to 20 mA –10 to +10 V
7 0 to 10 V 0 to 10 V
8 0 to 10 V –10 to +10 V
9 –10 to +10 V –10 to +10 V
0
9
7
8
4
6
1
5
3
2