324
Using Another Company’s Master Unit Appendix B
Table of Connection Type and Data Size Settings
The following table lists the I/O data sizes for each OMRON Slave as well as the supported connection types.
(A “Yes” indicates that the connection is supported; a “No” indicates that it is not.)
Slave group Model Connection type Data sizes
poll bit
strobe
change
of state
cyclic IN OUT
Transistor Remote I/O Terminals DRT1-ID08 Yes Yes No No 1 0
DRT1-ID08-1 Yes Yes No No 1 0
DRT1-ID16 Yes Yes No No 2 0
DRT1-ID16-1 Yes Yes No No 2 0
DRT1-OD08 Yes No No No 0 1
DRT1-OD08-1 Yes No No No 0 1
DRT1-OD16 Yes No No No 0 2
DRT1-OD16-1 Yes No No No 0 2
DRT1-MD16 Yes No No No 1 1
Transistor Remote I/O Terminals
with 3-tier I/O Terminal Blocks
DRT1-ID16T Yes Yes No No 2 0
DRT1-ID16T-1 Yes Yes No No 2 0
DRT1-ID16TA Yes Yes No No 2 0
DRT1-ID16TA-1 Yes Yes No No 2 0
DRT1-OD16T Yes No No No 0 2
DRT1-OD16T-1 Yes No No No 0 2
DRT1-OD16TA Yes No No No 0 2
DRT1-OD16TA-1 Yes No No No 0 2
DRT1-MD16T Yes No No No 1 1
DRT1-MD16T-1 Yes No No No 1 1
DRT1-MD16TA Yes No No No 1 1
DRT1-MD16TA-1 Yes No No No 1 1
Transistor Remote I/O Terminals
with Connectors
DRT1-ID32ML Yes Yes No No 4 0
DRT1-ID32ML-1 Yes Yes No No 4 0
DRT1-OD32ML Yes No No No 0 4
DRT1-OD32ML-1 Yes No No No 0 4
DRT1-MD32ML Yes No No No 2 2
DRT1-MD32ML-1 Yes No No No 2 2
Remote Adapters DRT1-ID16X Yes Yes No No 2 0
DRT1-ID16X-1 Yes Yes No No 2 0
DRT1-OD16X Yes No No No 0 2
DRT1-OD16X-1 Yes No No No 0 2
Sensor Terminals DRT1-HD16S Yes Yes No No 2 0
DRT1-ND16S Yes No No No 1 1
Temperature Input Terminals DRT1-TS04T Yes Yes No No 8 0
DRT1-TS04P Yes Yes No No 8 0
Analog Input Terminals DRT1-AD04 Yes Yes No No 8 0
DRT1-AD04H Yes Yes No No 8 0
Analog Output Terminals DRT1-DA02 Yes No No No 0 4
CQM1 I/O Link Unit CQM1-DRT21 Yes No No No 2 2