Appendix BSpecifications
155
Terminal Connections
I/O word “n”
CN1
I/O word “n+1”
CN2
B
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
COM0
+
NC
10
NC
11
NC
NC
8
9
10
11
12
13
14
15
COM1
+
5 VDC
AB
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
COM2
9
8
9
10
11
12
13
14
15
COM3
+
+
NC
10
NC
11
NC
NC
NC
12
+
A
1
2
3
4
5
6
7
8
9
10
11
12
NC
+
5 VDC
NC
12
NC
+
5 VDC
+
5 VDC
1
2
3
4
5
6
7
8
9
10
11
12
Note 1. I/O word “n” is determined by the unit number setting (n = IR 100 + 10 × unit number).
2. When pin 2 of the Unit’s DIP switch is ON, input points 08 to 15 in connector 2 are high-speed inputs.
DC Input Unit C200H-ID215 (32 Points)
Rated Input Voltage 24 VDC
Operating Input Voltage 20.4 to 26.4 VDC
Input Impedance
5.6 kW
Input Current 4.1 mA (at 24 VDC)
ON Voltage 14.4 VDC min.
OFF Voltage 5.0 VDC max.
ON Response Time 2.5 ms/15 ms max. (switchable; at 24 VDC, 25°C)
OFF Response Time 2.5 ms/15 ms max. (switchable; at 24 VDC, 25°C)
No. of Circuits 4 (8 points/common)
High-speed Inputs 8 points (connector 2 terminals 8 to 15, when set)
Pulse width: 1 ms/4 ms min. (switchable)
Internal Current Consumption 130 mA 5 VDC max.
Weight 300 g max.
Dimensions 130×34.5×100.5 (H×W×D, in millimeters)

Table of Contents