EasyManua.ls Logo

Omron SYSMAC C200HS - Page 197

Omron SYSMAC C200HS
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix BSpecifications
183
DIP Switch Settings
Set the DIP switch as described before for the various models of B7A Interface Units.
C200H-B7A22/12
Pin Function OFF ON
1 Transmission delay Standard (19.2 ms) High-speed (3 ms)
2 Transmission error process Hold status Reset Inputs
3 Input mode 16 inputs 15 inputs + error input
4 ERROR 1 indicator enable Disabled Enabled
5 ERROR 2 indicator enable Disabled Enabled
6 Not used. NA NA
C200H-B7A21
Pin Function OFF ON
1 Transmission delay Standard (19.2 ms) High-speed (3 ms)
2 Transmission error process Hold status Reset Inputs
3 Input mode 16 inputs 15 inputs + error input
4 ERROR indicator enable Disabled Enabled
5 Not used. NA NA
6 Not used. NA NA
C200H-B7A02
Pin Function OFF ON
1 Transmission delay Standard (19.2 ms) High-speed (3 ms)
2 Not used. NA NA
3 Not used. NA NA
4 Not used. NA NA
5 Not used. NA NA
6 Not used. NA NA
Transmission Delay
Pin 1 is used to set the transmission delay. The same delay is used for all words allocated to the Unit.
Set the transmission delay to match that of the B7A Link Terminal. A transmission error will occur if the same trans-
mission delay is not set.
The “3ms” indicator will be lit whenever the high-speed (3 ms) transmission delay is set.
Transmission Error Process
Pin 2 is used to turned ON to specify resetting input status when transmission errors occur. If pin 2 is turned OFF,
input status will be held when transmission errors occur.
The LOAD OFF indicator will be lit whenever pin 2 is turned ON.
Input Mode
Pin 3 is turned ON to specify use of only 15 inputs and the use of bit 15 as a Transmission Error Flag. If pin 3 is OFF,
16 normal inputs can be used.
The “15IN+ERR” indicator will be lit whenever pin 3 is turned ON.
ERROR Indicators
Pin 4 or pins 4 and 5 are turned ON to enable the ERROR, ERROR 1, and/or ERROR 2 indicators. These indica-
tors will not light even if a transmission error occurs if the corresponding pin is turned OFF.
Factory setting
(pins 4 and 5 ON)
Factory setting
(pin 5 ON)
Factory setting
(all pins OFF)

Table of Contents

Other manuals for Omron SYSMAC C200HS

Related product manuals