EasyManuals Logo

Omron SYSMAC C20P User Manual

Omron SYSMAC C20P
211 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #175 background imageLoading...
Page #175 background image
Appendix BProgramming Instructions
169
Name
Mnemonic
OperandsFunctionSymbol
Move
MOV(21)
MOV(21)
S
D
Transfers source data (S) (word or four–di-
git constant) to destination word (D).
S:
IR
SR
HR
AR
LR
TC
DM
#
D:
IR
HR
AR
LR
DM
Move NOT
MVN(22)
MVN(22)
S
D
Inverts source data (S) (word or four–digit
constant) and then transfers it to destina-
tion word (D).
S:
IR
SR
HR
AR
LR
TC
DM
#
D:
IR
HR
AR
LR
DM
BCD to
Binary
BIN(23)
BIN(23)
S
R
Converts four–digit, BCD data in source
word (S) into 16–bit binary data, and out-
puts converted data to result word (R).
S R
x10
0
x10
1
x10
2
x10
3
x16
0
x16
1
x16
2
x16
3
(BCD) (BIN)
S:
IR
SR
HR
AR
LR
TC
DM
R:
IR
HR
AR
LR
DM
Binary to
BCD
BCD(24)
BCD(24)
S
R
Converts binary data in source word (S)
into BCD, and outputs converted data to
result word (R).
x16
0
x16
1
x16
2
x16
3
x10
1
x10
2
x10
3
S R
(BIN) (BCD)
x10
0
S:
IR
SR
HR
AR
LR
DM
R:
IR
HR
AR
LR
DM
BCD Add
ADD(30)
ADD(30)
Au
Ad
R
CY CY
Adds two four–digit BCD values (Au and
Ad) and content of CY, and outputs result
to specified result word (R).
Au + Ad +
R
Au/Ad:
IR
SR
HR
AR
LR
TC
DM
#
R:
IR
HR
AR
LR
DM
BCD
Subtract
SUB(31)
SUB(31)
Mi
Su
R
Subtracts both four–digit BCD subtrahend
(Su) and content of CY from four–digit
BCD minuend (Mi) and outputs result to
specified result word (R).
CY CYMi – Su
R
Mi/Su:
IR
SR
HR
AR
LR
TC
DM
#
R:
IR
HR
AR
LR
DM

Table of Contents

Other manuals for Omron SYSMAC C20P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC C20P and is the answer not in the manual?

Omron SYSMAC C20P Specifications

General IconGeneral
BrandOmron
ModelSYSMAC C20P
CategoryController
LanguageEnglish

Related product manuals