EasyManuals Logo

Omron SYSMAC CS Series User Manual

Omron SYSMAC CS Series
316 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #101 background imageLoading...
Page #101 background image
69
Basic Procedure for Using the Loop Controller Section 1-5
Note Check the following points before you start Loop Controller operation.
a. The correct combination of Analog I/O Units must be mounted.
b. Analog Input/Output Units used in combination with the Loop Control
Board must be mounted correctly, and the unit number set on the front
panel of the Analog Input/Output Unit must match the unit number set
on the Field Terminal block. If the unit numbers do not match, in-
put/output (read/write) is performed on the data of another Special I/O
Unit (whose unit number is set on the Field Terminal block).
c. The correct defaults of the System Common block on the Loop Con-
troller must be set.
8. Execute the run/stop command on CX-Process Tool (Execute - Operation
- Monitor run status) or turn the PLC power OFF then back ON again.
Refer to CX-Process Tool Operation Manual.
Note When the CS1D-LCB05D is being used, the standby Loop Controller can take
up to 150 seconds (for duplex initialization) before starting operation after the
PLC power is turned ON. (The EXEC LED on the front and the DPL STATUS
LED will flash for 150 seconds and then will be lit.)
9. Check the LEDs on the front panel of the Loop Controller (RDY LED lit,
EXEC LED lit).
See 7-1 Errors and Alarm Troubleshooting.
5. Trial Operation
1,2,3... 1. Execute the run/stop command on CX-Process Tool (Execute - Operation
- Monitor run status) or turn the PLC power OFF then back ON again.
See 3-2 Description of Operations.
Refer to CX-Process Tool Operation Manual.
2. Monitor the run status on CX-Process Tool (Execute - Operation - Moni-
tor run status).
Execute the load rate check and other diagnostic checks.
Refer to the CX-Process Tool Operation Manual.
Note To disable inadvertent generation of analog signals when running of the Loop
Controller is started merely for checking the load rate, disconnect the analog
output connections.
3. Check the connections on CX-Process Tool (Validate action - Start).
Refer to the CX-Process Tool Operation Manual.
4. Set up and start CX-Process Tool.
Refer to CX-Process Tool Operation Manual.
5. Set the Set Point and other settings from CX-Process Tool or from SCADA
software.
Refer to the CX-Process Tool Operation Manual.
Peripheral port or RS-232C port
CPU Unit
Loop Control Board
Prepare function block data on
CX-Process Tool on the
computer.
Function block
data

Table of Contents

Other manuals for Omron SYSMAC CS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CS Series and is the answer not in the manual?

Omron SYSMAC CS Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CS Series
CategoryController
LanguageEnglish

Related product manuals