Page #297 background image
265
How to Use the Sequence Table Block Appendix B
Conditions
The following contact signals can be used for sequence table conditions.
Signal Notation on CX-
Process Tool
screen
Types Settings on CX-
Process Tool screen
Setting method Example
Input IN (source speci-
fication)
Contact input or
contact output
ITEMs from func-
tion blocks
Input Tab Page source
specification: Block and
ITEM
Select the block and
ITEM and select the
ITEM number from the
detailed information.
For block address
001 and ITEM 086:
001.086
CSV tag and tag
ITEM (contact
input or contact
output ITEM for
control or opera-
tion block)
Input Tab Page source
specification: Tag No.
Select the ITEM tag and
select the ITEM from
the detailed information.
For the A/M switch
for the Master01
CSV tag:
Master01.A_M
User link table
tag name (I/O
memory in CPU
Unit)
Input Tab Page source
specification: User link
table
Select the area type
and select the user link
table tag name from the
detailed
information.
For SW01 user link
table tag:
LNK007:SW01
Timer/counter
completion sta-
tus or status con-
tact, such as a
pre-alarm status
contact for a
timer/counter
Input Tab Page source
specification: Element
Specify the timer/
counter number and
select the status contact
from the detailed
information.
---
TBL (block
address)
Reference table Input Tab Page source
specification: Block and
ITEM
Select the block
address.
Rela-
tional
Expres-
sion
(parameter 1) <
(parameter 2)
(parameter) <
#(value)
ā€œ<ā€ can be
replaced with
other compari-
son symbols
Result of com-
parison for rela-
tional expression
Relational expression
types are set in the com-
mand classification on
the Relational
Expression Tab Page.
The same settings are
possible for parameters
1 and 2 as for the inputs
listed
above, i.e. Block and
ITEM, Tag No., user link
table, or element), or a
value
(constant) can be set.
Set the relational
expression (<, #, #, =, >,
or #) parameter 1, and
parameter 2.
For elements, specify
the number and then
select the present value
of the PV, the remaining
time, or the counter
value.
For a user link
table tag type value
equals 200:
(LNK005:type =
#200)

Table of Contents

Other manuals for Omron SYSMAC CS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CS Series and is the answer not in the manual?

Omron SYSMAC CS Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CS Series
CategoryController
LanguageEnglish

Related product manuals