How to Use the Sequence Table Block Appendix B
Actions
The following contact signals can be used for sequence table outputs.
Signal Notation on CX-
Process Tool
screen
Types Settings on CX-Process
Tool screen
Setting method Example
Output
(See note.)
OUT_H (destina-
tion): Holding contact
output operation
OUT_L (destina-
tion): Non-holding
contact output oper-
ation
OUT_P (destination):
Pulse contact output
operation
OUT_F (destina-
tion): Flashing con-
tact output operation
Function block
contact output
item
Output tab destination
specification: Block ITEM
Select the block ITEM
and select the ITEM
number from the
detailed information.
For block
address 001
and ITEM
086: 001.086
CSV tag and tag
ITEM
(Contact output
ITEM for control
and operation
blocks)
Output tab destination
specification: Tag No.
Select the ITEM tag
and select the tag
ITEM from the detailed
information.
For the A/M
switch for the
Master01
CSV tag:
Master01.A_
M
User link table
name (I/O mem-
ory in CPU Unit)
Output tab destination
specification: User link
table
Select the block ITEM
and select the ITEM
number from the
detailed information.
For Value1
user link
table tag:
LNK007:Valu
e01
Timer/counter
reset start, opera-
tion start/stop,
and pause com-
mands
Output tab destination
specification: Element
action (destination)
Select the area type
and select the link
table tag name from
the detailed informa-
tion.
---
Table Com-
mand
STEP(sequence
table block address,
step number)
Setting of a spe-
cific step in
another sequence
table
Table Command Tab com-
mand classification:
STEP(block address, step
number)
Block address and
step number
For block
address 702,
step 03:
70203
RUN(sequence table
block address)
Starting another
sequence table
Table Command Tab com-
mand classification:
RUN(block address)
Block address For block
address 702:
702
STOP(sequence
table block address)
Stopping another
sequence table
Table Command Tab com-
mand classification:
STOP(block address)
Block address For block
address 702:
702
Write to
ITEM
SET(value, destina-
tion)
Writing a con-
stant to a function
block ITEM write
parameter
Write to ITEM tab destina-
tion: Block ITEM
Select the block ITEM,
select the ITEM num-
ber from the detailed
information, and input
the write data (-32,000
to 32,000).
---
Writing a con-
stant to an CSV
tag and tag ITEM
(Contact output
ITEM for control
and operation
blocks)
Write to ITEM tab destina-
tion: Tag No.
Select the ITEM tag,
select the tag ITEM
from the detailed infor-
mation, and input the
write data (-32,000 to
32,000).
---
User link table
(writing a constant
to I/O memory in
the CPU Unit)
Write to ITEM tab destina-
tion: User link table
Select the area type,
select the user link
table tag from the
detailed information,
and input the write
data (-32,000 to
32,000: Input the
scaled value for the
user link table).
---

Table of Contents

Other manuals for Omron SYSMAC CS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CS Series and is the answer not in the manual?

Omron SYSMAC CS Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CS Series
CategoryController
LanguageEnglish

Related product manuals